Download Print this page

Manitowoc IB Series Parts & Service Communicator

Electronic bin thermostat control

Advertisement

Quick Links

The electronic bin thermostat control is used with ice machines on dispensers or ice machines with pure water
(reverse osmosis or de-ionized). Current production Ice Beverage (IB Model) machines also have the electronic bin
thermostat control replacing the mechanical bin thermostat control.The thermostat is intended to reduce overfill
and condensation issues. If an ice machine has an electronic bin thermostat control, a bin thermostat will be
mounted in the bin.
Bin Thermostat
ELECTRONIC BIN THERMOSTAT CONTROL
The temperature control opens the bin switch (or toggle
switch) circuit when ice contacts the sensor. When ice no
longer contacts the sensor, the circuit closes and the ice
machine starts.
Specifications
Setpoint Range: -30 to 212°F (-34 - 100°C)
CONTROL SETTINGS
Verify control is set properly before proceeding.
Display
Function
SP
Set Point
DIF
Differential
ASD
Anti-Short Cycle Delay
OFS
Temperature Offset
SF
Sensor Failure Mode
Positioning the Touchpad Jumpers
P5 Jumper
The P5 jumper position determines if the touchpad is
locked or unlocked. The control is factory locked; to unlock
move the jumper from one pin to two pins.
MANITOWOC ICE, INC.
Electronic Bin Thermostat Control
Preset Settings
40
1
1
0
1 - Cubers
0 - Nugget/Flake/Chiplet
Address - 2110 S. 26th St., P.O. Box 1720, Manitowoc, WI 54221-1720 USA
Telephone - 920-682-0161 • Service Fax - 920-683-7585 • Web Site - www.manitowocice.com
Parts & Service Communicator
RED LEAD
SENSOR
PROBE
BLACK
LEAD
SENSOR
PROBE
MATCH
WIRING
TO ICE
MACHINE
VOLTAGE
240V COM
Inside of Bin Thermostat Control
P4 Jumper
The P4 jumper labeled Jump 1 is used to set the control for
heating or cooling mode. Jump 2 is used to establish Set-
point at either cut-in or cutout. The Cubers use Diagram A
settings and Nugget/Flake/Chiplet use Diagram B
settings.
Cooling Mode
Diagram
A
Cut-In at Setpoint
Jump 1
Jump 2
Diagram
B
Cut-Out at Setpoint
Jump 1
Jump 2
Nugget/Flake/Chiplet
PSC003-04
KEYPAD
JUMPER
LOCATION
P5
P4
Jump 1
Jump 2
BIN SWITCH
or TOGGLE
SWITCH
WIRE
115V
NC
C
NO
BIN SWITCH
or TOGGLE
SWITCH
WIRE
Jumper on
Left Pins
Only
P4
Cubers
Cooling Mode
Jumper on
Left Pin Only
Jumper on
Both Pins
P4
03/06
P5
P4

Advertisement

loading

Summary of Contents for Manitowoc IB Series

  • Page 1 Jump 1 Left Pin Only Jump 2 Jumper on Both Pins Nugget/Flake/Chiplet MANITOWOC ICE, INC. Address - 2110 S. 26th St., P.O. Box 1720, Manitowoc, WI 54221-1720 USA Telephone - 920-682-0161 • Service Fax - 920-683-7585 • Web Site - www.manitowocice.com...
  • Page 2 Setting Control Setpoint Value To view and adjust setpoint, follow these steps: Important 1. Press MENU until the display flashes SP. Follow these troubleshooting procedures in the order presented. Do not skip any of the steps in 2. Press MENU again to display the existing setpoint the procedures.