Icvd Transformer Wiring; Icvd Interconnecting Wiring - Manitowoc Indigo Series Technician's Handbook

Hide thumbs Also See for Indigo Series:
Table of Contents

Advertisement

ICVD TRANSFORMER WIRING

ICVD transformers leave the factory wired for a 240V
supply voltage. When connecting to a 208V supply
voltage, the transformer must be rewired to maintain
a 24V secondary voltage. Failure to correctly wire the
transformer can result in premature transformer failure.
Refer to wiring diagrams for wiring details.

ICVD INTERCONNECTING WIRING

Indigo
interconnecting low voltage wiring (included with
Manitowoc line sets) to energize the contactor coil
and verify the LPCO & HPCO are closed. This circuit
also initiates a time delay whenever the LPCO or HPCO
open. Failure to properly wire the iCVD condensing
unit or ice machine head section will result in a non-
operational machine.
Wire Specifications:
18 AWG 5 Conductor, Single Strand, Plenum
Rated, UL rated to 300 volts.
Part Number STH026 6/15
Important
QuietQube
ice
machines
require
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents