ICVD TRANSFORMER WIRING
ICVD transformers leave the factory wired for a 240V
supply voltage. When connecting to a 208V supply
voltage, the transformer must be rewired to maintain
a 24V secondary voltage. Failure to correctly wire the
transformer can result in premature transformer failure.
Refer to wiring diagrams for wiring details.
ICVD INTERCONNECTING WIRING
Indigo
interconnecting low voltage wiring (included with
Manitowoc line sets) to energize the contactor coil
and verify the LPCO & HPCO are closed. This circuit
also initiates a time delay whenever the LPCO or HPCO
open. Failure to properly wire the iCVD condensing
unit or ice machine head section will result in a non-
operational machine.
Wire Specifications:
18 AWG 5 Conductor, Single Strand, Plenum
Rated, UL rated to 300 volts.
Part Number STH026 6/15