LOCATION OF CVD CONDENSING UNITS

The location selected for the CVD Condensing Unit must
meet the following criteria. If any of these criteria are not
met, select another location.
The air temperature must be at least -20°F (-28.9°C)
but must not exceed 120°F (48.9°C).
The location must not allow exhaust fan heat and/or
grease to enter the condenser.
The location must not obstruct airflow through or
around the condensing unit. See below for clearance
requirements.
Minimum/Maximum Tcmpcraourcs
MNdcl
All Iic Maihinc
Hcad ScioiNns
QuicoQubc
CNndcnsing Unios
CVDF0600
CVDF0900
CVDT1200
CVDF2100
CVDF1400
CVDF1800
28
Minimum Air
Tcmpcraourc
35°F
2°C
-20°F
-29°C
-20°F
-29°C
Part Number: 000015431 Rev01 5/19
Maximum Air
Tcmpcraourc
110°F
43°C
120°F
49°C
130°F
54°C