Instead, if the installation consisted of a horizontal vent coming
out at the back of the stove on a total distance of 4 feet,
followed by a tee and a 6-foot vertical rise, it would be
acceptable.
The
termination
is
within
the
allowable
configuration zone on the chart since it would have at least one
foot of vertical rise for each foot of horizontal run. Furthermore,
the total vertical rise is at least 3-feet high.
WARNING: To reduce the risk of smoke spillage there
should always be at least one foot of vertical rise for each
foot of horizontal run. In all cases, at least 3 feet of vertical
rise is needed.