MTU 8 V 4000 Lx2 xx Operating Instructions Manual page 84

Table of Contents

Advertisement

1.4540.012 – Valve Position Error
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.013 – High Elec Temp
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.014 – Elec Temp Fail High
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.015 – FGT Fail High
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.016 – Delta P Fail High
Red alarm. Initiated by TecJet.
Cause
Differential pressure at TecJet
too high.
1.4540.017 – FGP Fail High
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.018 – Coil Current Fail High
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
84 | Troubleshooting | MS150114/01E 2015-03
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
1. Check gas pressure.
2. Check TecJet for dirt.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.