Download Print this page

Avaya G700 Troubleshooting Manual page 6

Hide thumbs Also See for G700:

Advertisement

Alarms-LEDs-Traps
Symptom
Root Cause
Red LED on LED
Possible fault with
board is on. Major
the Media Gateway
Alarm is present.
Processor (MGP) or
Media Modules.
The CPU
temperature sensor
has exceeded its
shutdown threshold.
The system is about
to begin controlled
shutdown
Red LED on LED
Possible fault with
board is on. Major
the Media Gateway
Alarm is present.
Processor (MGP) or
The command
Media Modules.
show faults
The voltage reading
indicates that the
at the +5.1v power
fault in the Root
source serving the
Cause column is
MG Processor is
out of tolerance.
present.
G700 Troubleshooting
1. Verify there are faults in the system. Use the G700's Media Gateway Processor (MGP) Command Line
Interface (CLI) command show faults to display any faults on the G700.
2. If a temperature alarm, turn off the G700 Media Gateway and allow it to cool.
3. If faults do appear, then resolve them by checking for fan alarms.
4.If it is a fan alarm, then check for voltage alarms. Issue the MGP CLI command show voltages to determine
voltages for the Media Modules and other components of the G700. Low voltage may be responsible for slower
fans. Voltage may be reduced by a short in one of the Media Modules or a bad power supply.
5. Systematically, remove each Media Module to determine if one of the Media Modules is responsible for
reducing the voltage levels. Replace faulty Media Module.
6.If fans are faulty then replace the entire G700. Fans are not field replaceable.
1. Check for voltage alarms. Issue the MGP CLI command show voltages to determine voltages for the Media
Modules and other components of the G700. Low voltage may be responsible for slower fans. Voltage may be
reduced by a short in one of the Media Modules or a bad power supply.
2. Systematically, remove each Media Module to determine if one of the Media Modules is responsible for
reducing the voltage levels. Replace faulty Media Module.
3. If fans are faulty then replace the entire G700. Fans are not field replaceable.
4. If the alarm clears in 10-20 seconds, it was a probable voltage spike. Do not replace the G700.
5. If a brown-out condition is suspected, use a power monitor to monitor the power line.
Resolution
Page 3
7/5/2002 4:35 PM

Advertisement

loading