Advertisement

4. Install vent pipe so that it can expand and contract freely as the temperature changes.
Support the vent pipe according to applicable codes and vent manufacturer's instructions.
Pipe support must allow the vent pipe free movement out and back, from side to side,
or up and down as necessary, without putting a strain on the heater or vent body. It is
recommended to slope the horizontal pipe down to condensate trap at least 2cm/M (1/4
in per foot). Install "Approved" condensate drains at low points where condensate might
collect. Plumb condensate drains to a drain through hard piping or high-temperature tubing
such as silicone rubber or EPDM rubber – do not use vinyl or other low temperature tubing.
Follow drain manufacturer's installation instructions.
5. Use an "Approved" firestop for floor and ceiling penetrations. Use an "Approved" thimble
for wall penetrations. Use an "Approved" roof flashing, roof jack, or roof thimble for all roof
penetrations. Do not fill the space around the vent (that is, the clear air space in the thimble
or firestop) with insulation. The roof opening must be located so that the vent is vertical.
6. Vent Termination – Vertical (See Figures 14, 15 and 16), for height of vent termination above
the roof. Use an "Approved" vent terminal specified by local and national codes and your
manufacturer's instructions. A roof termination must be vertical.
7. Make sure entire installation is sealed according to approved standard.
Vent Cap and
Riser Furnished
by Installer
Side
Wall Vent
Figure 15.
Vent
Termination
0.3 M (1 in) Minimum
above snow or
finished grade
(whichever is
higher)
Figure 17.
Chimney or Gas Vent
Outlet Air
Opening
Inlet Air
Heater
Opening
1.2 M (4 in) Min.
1.2 M (4 in) Min.
1.2 M
(4 in)
Min.
Gas Meter
Forced Air
Inlet
r
7.6 cm (3 in) minimum clearance if
horizontal distance to
exhaust opening is less
than 3.3 M (10 ft).
Chimney or Gas Vent
Vent Cap and
Riser Furnished
by Installer
Side
Heater
Wall Vent
1.2 M (4 in) Min.
Vent
Termination
0.3 M (1 in) Min.
Section 3. Installation
I pg 28
Outlet Air Opening
Inlet Air Opening
Figure 16.
Max. 304 mm (12 in)
Min. 76 mm (3 in)
Vent
Termination
At least 2.1 M (7 in)
above grade
adjacent
to public
walkways