COMBUSTION AIR SUPPLY
For indoor installation, the heater location must provide sufficient air supply for proper
combustion and ventilation of the surrounding area (in accordance with AS/NZS 5601.1).
The minimum requirements for the air supply specify that the room in which a heater is installed
should be provided with two permanent air supply openings; one within 30 cm (12 in) of the
ceiling, the other within 30 cm (12in) of the floor for combustion air, in accordance with the AS/
NZS 5601.1 as applicable, and any local codes that may apply. These openings shall directly,
or through duct, connect to outdoor air.
Waterco Limited does not recommend indoor installations that do not provide combustion air
from outside the building.
Air Supply Requirement Guide for Turbotemp Heaters
Minimum Net Free Open Area for Each Opening*
All Air From Inside Building
Model
Combustion
200 sq. in.
200
1290 sq. cm.
325 sq. in.
300
2097 sq. cm.
400 sq. in.
400
2580 sq. cm.
* Area indicated is for one of two openings; one at floor level and one at the ceiling.
(Square Inches/Centimeters)
Vent
200 sq. in.
1290 sq. cm.
325 sq. in.
2097 sq. cm.
400 sq. in.
2580 sq. cm.
Section 3. Installation
All Air From Outside Building
Combustion
50 sq. in.
323 sq. cm.
80 sq. in.
516 sq. cm.
100 sq. in.
645 sq. cm.
I pg 20
Vent
50 sq. in.
323 sq. cm.
80 sq. in.
516 sq. cm.
100 sq. in.
645 sq. cm.
Table 4.