Inverter Operation Status Control - Mitsubishi Electric 700 Series Programming Manual

700 series plc function programming manual
Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

1.7.4

Inverter operation status control

Device No.
D9148
D9149
(1) Inverter operation status control (D9148)
Device for inverter operation status control. The operation of the inverter can be
controlled by turning on/off (1, 0) bits b0 to b11 of D9148.
All bits are factory-set to "0".
Example: When 5 is set to D9148, bits b0 and b2 are 1 (ON), and STF and RH
therefore turn on to give a high-speed forward rotation command.
CAUTION
As in the external input terminals, functions can be assigned to the bits of
D9148 using Pr.178 to Pr.189. However, no function can be assigned to SQ
(sequence RUN setting: 50).
Name
Inverter operation status control Always
Inverter operation status control
enable/disable
B15
B12B11
B8B7
0
0
0
0
0
0
0
Invalid
Inverter Status Monitoring, Special Registers
Data Access Enable Condition
Note that this function is enabled in
the external/NET operation mode.
(Not enabled in the PU
operation mode.)
B4B3
B0
0:OFF
0
0
1
0
1
1:ON
STF (Pr.178)
STR (Pr.179)
RH (Pr.182)
RM (Pr.181)
RL (Pr.180)
JOG (Pr.185)
RT (Pr.183)
AU (Pr.184)
CS (Pr.186)
MRS (Pr.187)
STOP (Pr.188)
RES (Pr.189)
for Control
1
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a700

Table of Contents