Internal Relay (M) Device Map; Data Register (D) Device Map; Special Relays - Mitsubishi Electric 700 Series Programming Manual

700 series plc function programming manual
Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

Device Map
1.6.2

Internal relay (M) device map

Device No.
M0 to M63
Use freely on user side.
1.6.3

Data register (D) device map

Data
Inverter Pr.
Register (D)
Number
D0 to D99
Use freely on user side.
Pr.506 to
D100 to D119
Pr.515
1.6.4

Special relays

The special relays are internal relays with special applications and therefore should
not be switched on-off in the program.
Number
M9008
Self-diagnostic error
M9010
Operation error flag
M9011
Operation error flag
M9036
Normally ON
M9037
Normally OFF
On only for 1 scan after
M9038
RUN
Off only for 1 scan after
M9039
RUN
Inverter operation status
M9200
control flag (STF)
Inverter operation status
M9201
control flag (STR)
Inverter operation status
M9202
control flag (RH)
Inverter operation status
M9203
control flag (RM)
Inverter operation status
M9204
control flag (RL)
Inverter operation status
M9205
control flag (JOG)
Inverter operation status
M9206
control flag (RT)
Inverter operation status
M9207
control flag (AU)
Inverter operation status
M9208
control flag (CS)
Inverter operation status
M9209
control flag (MRS)
Inverter operation status
M9210
control flag (STOP)
12
User parameters. Use freely on user side.
Name
Turned on by self-diagnosed error.
Turned on by an instruction execution error.
Turned off when error is removed.
Turned on by an instruction execution error.
Remains on after normal status is restored.
M9036 and M9037 are turned on and off independently
of STOP or RUN.
M9038 and M9039 change depending on the STOP or
RUN status. In other than the STOP status, M9038 is on
for one scan only and M9039 is off for one scan only.
Control the STF terminal of the inverter from PLC
function
Control the STR terminal of the inverter from PLC
function
Control the RH terminal of the inverter from PLC
function
Control the RM terminal of the inverter from PLC
function
Control the RL terminal of the inverter from PLC function
Control the JOG terminal of the inverter from PLC
function
Control the RT terminal of the inverter from PLC function
Control the AU terminal of the inverter from PLC
function
Control the CS terminal of the inverter from PLC
function
Control the MRS terminal of the inverter from PLC
function
Control the STOP terminal of the inverter from PLC
function
Description
Parameter Name
Description
Reference
Page
38