System Configuration

1.3 System Configuration

The following shows the system configuration for use of the PLC function.
<System configuration example>
GX Developer:
Programming tool
3-phase AC
power supply
Communication specifications
Set the following setting in communication parameters of the inverter.
Inverter Parameter
Pr.118 PU communication speed
Pr.119 PU communication stop bit length
Pr.120 PU communication parity check
Pr.122 PU communication check time
interval
REMARKS
•For futher details, refer to the Inverter instruction manual (applied).
POINT
•Support GX Developer ver.8.0 or more
•GX Developer Setting
PLC series
PLC type
[Project data list]→[Parameter]→[PLC parameter]→[A parameter]
→«Memory capacity» tab→"Program capacity"→"Sequence"→"main"
REMARKS
•Refer to the Inverter instruction manual (applied) for wiring.
•Refer to the GX Developer manuals for the specifications related to GX Developer and the
personal computer that uses GX Developer.
GX Developer Version xx Operating manual
GX Developer Version xx Operating manual (startup)
•The programming tool that can be used is GX Developer only. (The A6GPP, A7PHP, etc.
cannot be used.)
4
PU connector
RS-232C/
RS-485
converter
GX Developer Setting
96 (9600bps)
0 (data length: 8 bits, stop
bit: 1 bit)
1 (with odd parity check)
9999 (without
communication check)
ACPU
A0J2H
FR-A700
Inverter initial setting
192 (19200bps)
1 (data length: 8 bits, stop
bit: 2 bit)
2 (with even parity check)
9999 (without
communication check)
Motor
1k step