Analog I/O Function; Analog Input; Analog Output - Mitsubishi Electric 700 Series Programming Manual

700 series plc function programming manual
Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

1.10 Analog I/O function

1.10.1 Analog input

Analog input value of termianl 1, 2, 4 can be read from D9245 to D9247.
Device
Terminal Name
No.
D9245 Terminal 1 input
D9246 Terminal 2 input
D9247 Terminal 4 input
Actual read processing is performed at the END processing of the sequence.
REMARKS
Full-scale value of analog input is determined by the setting of Pr. 73 Analog input selection, Pr.
267 Terminal 4 input selection. Refer to the inverter instruction manual (applied).

1.10.2 Analog output

Analog output from each terminal can be performed by setting value on D9251 to
D9254.
Output from PLC function can be performed by setting "7" in output signal selection
parameters of each terminal (terminal FM: Pr. 54, terminal AM: Pr. 158, terminal AMO,
AM1: Pr. 306, Pr. 310).
Device
Terminal Name
No.
D9251 Terminal FM
D9252 Terminal AM
Terminal AM0
D9253
(FR-A7AY)
Terminal AM1
D9254
(FR-A7AY)
Actual read processing is performed at the END processing of the sequence.
REMARKS
High speed pulse train output (Pr. 291) from terminal FM can be performed. (Refer to the
inverter instruction manual (applied).)
Setting
Data Access Enable
Unit
Condition
0.1%
0.1%
Always
0.1%
Setting
Data Access Enable
Unit
Condition
0.1%
0.1%
0.1%
Always
0.1%

Analog I/O function

39
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a700

Table of Contents