SUPPORTED DEVICE AND COMMAND CLASSES

Z-Wave Device Classes
Generic Device Class
Specific Device Class
Basic Device Class
Z-Wave Command Classes
Manufacturer Specific
Command Class
Version Command Class
Multi Level Sensor
Command Class
Basic Command Class
Implemented Device Classes
THERMOSTAT GENERIC DEVICE CLASS
THERMOSTAT GENERAL V2
ROUTING SLAVE
Description
Secure Manufacture ID
Provides the version number of the Software
The SRT323 will respond to the Multilevel Sensor
GET command with a Multilevel Sensor REPORT.
This report can be requested or sent unsolicited to
the nodes in Group 5. If the temperature sensor
functionality is disabled, the SRT323 will report 0x8000.
The Basic Command Class is mapped to the Setpoint
Command Class. The unit shall respond to the GET
command with a REPORT containing 0x00 if the
thermostat is not in comfort mode (5°C) or 0xFF if the
thermostat is in comfort mode (any other supported
temperature).
SET command ON (0x01 – 0x64 or 0xFF) sets the
setpoint to 21°C. SET command OFF (0x00) sets the
setpoint to 5°C. Any other value is ignored."