IMMEDIATE
REGEN
SET
RELAY 1 "TIME"
TRIGGER
SET
RELAY 1 SET POINT
SET
RELAY 1 DURATION
3:00
SET
RELAY 1 "GALLONS"
TRIGGER
SET
RELAY 1 SETPOINT
SET
RELAY 1 DURATION
0:01
SET
RELAY 1 "REGEN GALLONS"
TRIGGER
SET
11
STEP 11 S – Set Regeneration Time Options using the  or  button. If value is set to:
Step 11S
• "IMMEDIATE" means regeneration will occur immediately when the gallons capacity reaches 0
(zero)
Factory Setting is IMMEDIATE. Press NEXT to go to Step 12S. Press REGEN to return to previ-
ous step.
Step 12S
Step 13S
10
MIN
Step 14S
MIN
Step 15S
Step 16S
1
GAL
Step 17S
MIN
Step 18S
GAL
STEP 12 S – Set Relay to activate by Time, Gallons, Regen Gallons, Lockout,
Off or Service Alarm by using  or  buttons. A relay can be used to operate a
chemical feed pump or solenoid, etc. The choices are:
• Relay Triggered on Time - Relay activates after set number of minutes after start
of regeneration. Start of regeneration is defined by first backwash cycle, dn
brine or up brine, whichever is first. Relay deactivates after set time. Press
NEXT for programming.
• Relay Triggered on Gallons - Relay activates every set number of gallons
while in service and deactivates after set time. Press NEXT to go to 16S for
programming.
• Relay Triggered on Regen Gallons - Relay activates after set number of gallons
in service or gallons used during regeneration and de-activates after set time
or when meter stops registering flow, whichever comes first. Press NEXT to
go to 19S for programming.
• Service Alarm - Relay activates on service alarm setting: gallons, time or both,
see step 21S. Relay deactivates when alarm is reset.
• Relay Triggered for Lockout - Relay is activated at set number of minutes
before or after regeneration start. Regeneration start is the first backwash or
draw cycle. Selection of energizing relay for complete regeneration cycle is
available by selecting REGEN for time setting, see step 22S.
• Off - If off is selected, Steps 13S – 24S will not be shown. Factory setting
= OFF. Press NEXT to go to step 25S or other selection for relay settings, or
21S if OFF selected.
STEP 13 S – If off was selected in previous step, this screen does not appear.
Time chosen to Activate Relay, use up and down arrows to set # of minutes
AFTER START OF REGEN to activate relay. Start of regeneration is defined as
first Backwash or Regenerant Draw mode. Time Range = 1 – 500 minutes. Press
NEXT to go to Step 14S.
STEP 14 S – Use Up and Down arrows to set duration of relay activation in minutes.
Range is 0:01 (1 second) to 500:00 (500 minutes). Press NEXT to go to Step 25S.
Press REGEN to return to previous step.
STEP 15 S – Gallons chosen to activate relay. If Off or Time was selected in
previous steps, this screen does not appear. Press NEXT for trigger programming.
STEP 16 S – Use up and down arrows to set # of gallons per relay activation.
Range = 0.1 – 20,000 gallons. Press NEXT for Relay Duration. Press REGEN to
return to previous step.
STEP 17 S – Use up and down arrows to set duration of relay activation in minutes.
Range = 0:01 (1 second) - 500:00 (500 minutes). Press NEXT to go to Step 25S.
Press REGEN to return to previous step.
STEP 18 S – REGEN gallons chosen to activate relay. Relay activates after set
number of gallons have been used in service or during regeneration and then de-
activates after set period of time or after flow stops, whichever comes first. Press
NEXT to go to Step 19S.