5. REMOTE TERMINAL AND SUPERVISORY NETWORK

5.1 Remote display terminal

The display terminal can be detached from the humidifi er and moved up
to 30 m (98 feet) away.
2
1
M6
M10
3
UEY
esc
2
2
1
M8
1
2
Key:
1 telephone cable 6 wires (up to
10 m (33 ft)
2 two EMC fi lters (code 0907858AXX) to be applied to the ends of the
telephone cable;
3 remote display terminal.
Note: to fi ll the empty space left by the display terminal on the
humidifi er, use CAREL kit code HCTREW0000.
(1)
For lengths greater than 10 m (33 ft) use shielded cable with the shield
connected to PE both on the terminal side and the controller side
2
1
3
2
1
3
2
1
3
2
M11
M14
M7
2
1
2
1
JS6
M3
M9
J1
M12
M1
M2
M5
1 2
1 2 3
1
2
3
4
5
6
7
1
2
Fig. 5.a
(1
distance);

5.2 RS485 supervisory network (M1.1-M1.3)

M.1.1 M.1.2 M.1.3
per modelli
UEY*000/UEY*100
+ - G0
Rx- / Tx -
Rx+ / Tx +
Important: for the RS485 connections in household (IEC EN 55014-1)
and residential (IEC EN 61000-6-3) environments, use shielded cable
(with shield connected to PE both on the terminal side and the controller
side)
with maximum shielded cable length: specifi ed by the EIA RS485
protocol, equivalent to European stan-dard CCITT V11, using shielded
twisted pair cable, AWG26, 485 input stage impedance 1/8 unit-load (with
this confi guration, a maximum of 256 devices can be connected) laid in
separate conduits from the power cables
17
ENG
per modelli UEY*200
Fig. 5.b
"UE BASIC" +03U0042EN - rel. 1.3 - 10 May 2013