code display and
var. code
meaning
symbol
I89
E0
-
1008Hex
calibration parameter
software verifi cation
errora
E1
-
1004Hex
parameter confi guration
error
EH
1010Hex
excess current
EP
1020Hex
no production
CY
3001Hex
cylinder life pre-alarm
EF
2004Hex
no water
Ed
2008Hex
failed drain
CP
3004Hex
cylinder being depleted
signal
CL
3008Hex
cylinder depleted signal
EA
3002Hex
foam
E2
3010Hex
memory backup fails
Mn
1001Hex
end of cylinder life
8. ALARMS
causes
solution
internal memory error
if the problem persists,
contact the CAREL service
center
error in the parameters
if the problem persists,
user
contact the CAREL service
center
over-current at the
1. check the operation of
electrodes;
the drain pump
probable electrode
2. check the seal of the
or
malfunction
water
fi ll electrovalve when
conductivity temporarily
not energised
too high (especially
3. drain part of the
when starting after a
water and re-start
short stop)
excessive reduction in
Perform maintenance
production , or cylinder
on the cylinder
completely depleted
or water
the cylinder full limit of
perform maintenance and/
1500 h (default)
or replace the cylinder
Check:
•
water supply and fi ll
valve;
•
whether
the
drain is open;
•
blockage of the fi lter on
the fi ll solenoid valve;
•
whether
excessive backpressure in
steam outlet, preventing
the fl ow of water into the
cylinder by gravity;
•
that the steam outlet
hose is not choked or
that there are no pockets
of condensate;
•
that the power cables
are connected to the
cylinder
check the drain pump and
drain connection
cylinder life ending,
perform maintenance and/
or replace the cylinder
cylinder life ended, perform
maintenance and/or
replace the cylinder
excessive foam in the
1. drain the water supply
cylinder during boiling.
lines
the formation of foam
2. clean the cylinder
is generally due to the
3. check for the presence of
presence of surfactants
softeners
in the water (lubricants,
(in this case, use another
solvents, detergents,
type of water
water treatment
or reduce the softening)
agents, softeners) or an
excessive concentration
of dissolved salts.
internal memory error
if the problem persists,
contact the CAREL service
center
the cylinder has exceeded
the limit of 2000 hours,
replace the cylinder
21
reset (press) alarm relay
activation
--
yes
--
yes
AUTO
yes
ESC
yes
ESC
no
(the alarm is
reactivated
after 50 hrs)
automatic
yes
(after 10
(in 10
minute
minute
manual
waiting time)
waiting
time)
there
is
ESC
yes
AUTO
no
AUTO
no
ESC
no
--
no
reset hour
yes
counter
"UE BASIC" +03U0042EN - rel. 1.3 - 10 May 2013
ENG
eff ect
red LED signal
on board (*)
(if terminal not
connected)
humidifi cation
3 fast fl ashes
stopped
humidifi cation
4 fast fl ashes
stopped
humidifi cation
2 fast fl ashes
stopped
humidifi cation
4 slow fl ashes
stopped
signal only
7 fast fl ashes
humidifi cation
3 slow fl ashes
stopped for 10
minutes only
humidifi cation
5 slow fl ashes
stopped
signal only
6 slow fl ashes
signal only
10 slow fl ashes
signal only
9 slow fl ashes
signal only
6 fast fl ashes
humidifi cation
8 fast fl ashes
stopped