Output tolerance specifications

Source of power
Utility power (nominal
range)
Battery power

Output feature specifications

Feature
Online efficiency
Voltage wave shape
Surge suppression
Noise filtering

Battery specifications

Feature
Type
Voltage
Charging

Battery runtime for NA/JPN model

Load, W (percent)
20
50
80
100

Battery runtime for INTL model

Load, W (percent)
20
50
80
Regulation
-10% to +6% of nominal output voltage rating
(within the guidelines of the Computer Business
Equipment Manufacturers Association)
±5% of nominal output voltage rating
Specification
94% nominal input voltage
Sine wave; 5% THD with typical PFC load
High-energy 6500 A peak
MOVs and line filter for normal and common mode
use
Specification
Each model contains maintenance-free, sealed, valve
regulated lead-acid batteries with an 8-year minimum float
service life at 25°C (77°F).
The battery modules have a battery string voltage of 240
V.
Complete charge takes no more than 48 hours.
Approximately 3 hours to 80 percent capacity at default
nominal utility voltage and no load.
Estimated battery
runtime (minutes)
59
19
9
7
Estimated battery
runtime (minutes)
49
15
7
Runtime with one ERM
(minutes)
169
61
31
24
Runtime with one ERM
(minutes)
138
49
25
Runtime with two ERMs
(minutes)
303
106
60
46
Runtime with two ERMs
(minutes)
247
85
48
Specifications 45