Configuration setting (VAC)
208
230
240
Output tolerance specifications
Source of power
Utility power (nominal
range)
Battery power
Output feature specifications
Feature
Online efficiency
Voltage wave shape
Surge suppression
Noise filtering
Battery specifications
Feature
Type
Voltage
Charging
Battery runtime
Load, percent
20
50
80
100
Available nominal output voltage (VAC)
208
230
240
Regulation
-10% to +6% of nominal output voltage rating
(within the guidelines of the Computer
Business Equipment Manufacturers
Association)
±5% of nominal output voltage rating
Specification
94% nominal input voltage
Sine wave; 5% THD with typical PFC load
High-energy 6500 A peak
MOVs and line filter for normal and common mode
use
Specification
12 V, 5 AH, sealed, maintenance-free, rechargeable, valve
regulated lead-acid batteries with a 3-5 year service life at
25°C (77°F).
The battery modules have a battery string voltage of 120 V.
Complete charge takes no more than 24 hours. After
approximately 4 hours, the batteries reach 90% charge at
default nominal utility voltage and no load.
Estimated battery
runtime
40 minutes
12 minutes
6.5 minutes
5 minutes
Runtime with one ERM
120 minutes
45 minutes
30 minutes
20 minutes
Runtime with two ERMs
250 minutes
100 minutes
60 minutes
40 minutes