Superior DRC3035DEN Installation And Operation Instructions Manual page 36

Direct-vent gas fireplacesdrt3000 and drc3000 series
Table of Contents

Advertisement

Innovative Hearth Products
Superior
DRT/C3000 Series Direct-Vent Gas Fireplaces
TM
Vertical or Horizontal Venting Using Secure Flex Kits and Components
Secure Flex venting kits and components may be used in any other vent installation where rigid Secure Vent
direct-vent components can be used. All restrictions, clearances and allowances pertaining to rigid vent also apply to
flexible vent. Do NOT modify Secure Flex kits . Also, do NOT join separate sections of flex vent together. Secure Flex
kits can be installed on the end of a Secure Vent (SV4.5) rigid vent run, provided that doing so does not violate any
of the venting length, height, routing, horizontal to vertical ratio requirements, or clearance considerations detailed in
this manual. When combined, a rigid vent should not be installed between two flexible vents.
Secure Flex kits come with an included adaptor that can be installed on the fireplace collar or the inclined channel
end of the last Secure Vent (SV4.5) vent section in a rigid system in the exact same fashion as any other Secure Vent
section. Align the dimpled end of the adaptor over the previously installed section or fireplace collar, adjusting the
radial alignment until the four locking dimples of the adaptor are aligned with the inlets of the four incline channels of
the last vent section or collar. Push on the adaptor until it is fully engaged, then twist the adaptor clockwise running
the dimples down and along the incline channels until they seat at the end of the channels.
Figure 28: Flexible Vent Adaptor
NOTE: Outer vent pipe is pulled away
to show inner vent pipe details.
1. Install the Inner Flex Pipe.
2. Install the outer Flex Pipe.
36
Apply ONLY MIL-PAC BLACK
HIGH TEMPERATURE
SEALANT (P/N 10K81) to
the outside surface of both
collars of the adaptor (fill the
grooves of the outer collar to
be covered by the flexible pipe)
and slide the flexible vent over
the inner and outer adaptor
collars
1 3/4" (44 mm) flexible
vent and adaptor outer
collar overlap
Adaptor (SV4.5RF)
a. Install the small gear clamp loosely around the inner flexible vent, then push it back out of the way.
b. Apply a bead of Mill-Pac Black (700 °F) high temperature sealant (P/N 10K81) to the inner adaptor collar,
approximately 1/2" from the end.
c. Pull and extend the inner flexible vent.
d. Slide the inner flex vent over the adaptor collar at least 1 3/4".
NOTE: Ensure the flex vent is free from damage or tears.
e. Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor inner collar
approximately 3/4" from the end of the flex.
f. Install three (3) screws 120° apart through the flexible vent and into the adaptor collar just below the gear
clamp to provide additional security to the connection.
a. Install the large gear clamp loosely around the outer flexible vent pipe, then push it back out of the way.
b. Apply a bead of Mill-Pac Black (700 °F) high temperature sealant (P/N 10K81) to the outer adaptor collar.
Cover to the grooves of the collar that extend approximately 1" from the end and to the flat surface,
approximately 1 3/8" from the end.
c. Pull and extend the outer flexible vent.
d. Slide the outer flexible vent over the adaptor collar. Ensure the flexible vent completely engages the adaptor collar
1 3/4" from the end, and that it is free from damage or tears.
Securing screws
in three (3) places
through perforation
and into the pipe
1 3/4" (44 mm) flexible
vent and adaptor inner
collar overlap
Securing screws
in three (3) places
through perforation
and into the pipe
Attach adaptor to vent collar or Secure Vent sections
Figure 29: Flexible Vent
Flexible vent
Flexible vent section
Gear clamps
Shown here: 36" Flex Connector Kit
36" of flex with two adaptors for mating
two rigid sections of vent together.
Installation
900285-00 05/2015
(SV4.5)
®
5" (127 mm)
radius minimum
(H7748)