Table 10: Fireplace Framing Specifications
Model
A *
33 3/4
33" Models
(857)
35 3/8
35" Models
(899)
40 3/8
40" Models
(1026)
45 3/8
45" Models
(1153)
C = Minimum height of top vent installations
E = Minimum height of rear vent installations
* Minimum opening size; additional 1/8" per side is recommended.
NOTE: Framing specifications do NOT apply for flexible venting.
When using flexible venting, refer to the kit requirements for
framing specifications.
Table 11: Fireplace Framing Specifications—Corner Installation with Horizontal Termination
Model
A
B
33 3/4
51 1/4
33"
(857)
(1302)
35 3/8
59 1/2
35"
(899)
(1511)
40 3/8
63 13/16
40"
(1025)
(1621)
45 3/8
70 3/8
45"
(1153)
(1788)
Table 12: Fireplace Specifications
F
G
Top View
Model
A
B
33" Models
30 1/8 (765)
26 1/4 (667)
35" Models
32 1/8 (816)
28 3/4 (730)
40" Models
37 1/8 (943)
33 1/4 (845)
45"Models
37 1/8 (943)
33 1/4 (845)
B
C
D
34 1/4
36 7/8
14 1/2
(845)
(930)
(368)
36 1/4
38 3/4
18
(895)
(984)
(447)
41 1/4
43 3/4
18
(1048)
(1111)
(447)
41 1/4
43 3/4
18
(1048)
(1111)
(447 )
C
D
E
36 1/4
25 5/8
12 1/8
(921)
(651)
(308)
42 1/16
30 1/4
14 1/4
(1068)
(768)
(362)
45 11/32
33 3/16
15 7/8
(1152)
(818)
(403)
49 3/4
35 1/4
17 1/2
(1264)
(895)
(445)
NOTE: When finishing the area around the hood, 5/8" clearance above hood is required for hood installation.
E
I
A
D
K
H
Front View
C
D (door)
18 5/16 (465)
30 1/2 (775)
33 5/8 (854)
22 1/4 (565)
32 3/8 (822)
35 1/4 (895)
27 1/4 (692)
37 3/8 (949)
40 1/4 (1022)
27 1/4 (692)
42 3/8 (1076)
45 1/4 (1149)
E
NOTE: Dimension "D" is the
required framing depth when
19 5/8
(499)
the finish material (drywall)
thickness is 1/2" (13mm).
23 3/8
(594)
Vent Framing—Top Vent
with One 90° Elbow
28 1/4
(717)
28 1/4
(717)
B
1/2 A
Inches (millimeters)
F
5 1/2
(140)
6 5/8
(168)
8 1/2
(216)
C
10 1/4
(260)
Back wall of chase/enclosure (including finishing materials)
C
B
Blower
access panel
Left Side View
E
F
G
21 7/8 (556)
10 15/16 (278)
25 (635)
12 1/2 (317)
30 (762)
15 (381)
35 (889)
17 1/2 (445)
Framing
construction to be
10 1/2
2 x 4, or larger.
(267)
7 (178)
5 1/8
(130)
C
E
D
A
E
A
B
Hood
Junction
box access
Gas line
access
Right Side View
H
I
J
31 (787)
5 3/4 (146)
14 (356)
32 7/8 (835)
6 7/8 (175)
17 (432)
37 7/8 (962)
6 7/8 (175)
17 (432)
42 7/8 (1089)
6 7/8 (175)
17 (432)
Installation