8.1

UPS Connections

Terminal Blocks 150, 225kVA
1
2
3
00 o 0 00
00 o 0 00
U
v
w
ACINPUT
3-phase 3-wire
The terminals shown are located at the bottom inside of the 150/225kVA UPS. External cable
size is recommended in the Table 8.1/8.2.
Table 8.1
Recom mended Cable Size and Tightening Torque for 1 50kVA UPS
The tightening torque m ust be g reater than 90 percent of the recom mended torque.
Block Number
1
2
3
4
5
6
7
8
9
10
11
12
13
4
5
6
00 00
00
00 00
00
U
v
w
BYPASS INPUT
3-phase 4-wire
Cable Size and Tightening Torque for 150kVA UPS
(Only copper wires allowed)
Cable Size
AW G 3/0
AW G 3/0
AW G 3/0
AW G 3/0
AW G 3/0
AW G 3/0
AW G 3/0
AW G 3/0
AW G 3/0
AW G 3/0
AW G 3/0
Two AWG 3/0
Two AWG 3/0
NOTE: Maxi m u m cable size is 350MCM
7
8
9
00
00
00 0 0
00
00
00
N
U
v
ACOUTPUT
3-phase 4-wire
or larger
or larger
or larger
or larger
or larger
or larger
or larger
or larger
or larger
or larger
or larger
or larger
or larger
- 1 9 -
6F3H1048
10
11
12
o 0
0 0 00
o 0
o 0
o 0 00
N
w
BATTERY
Tightening Torque
275 in-Ibs
275 in-Ibs
275 in-Ibs
275 in-Ibs
275 in-Ibs
275 in-Ibs
275 in-Ibs
275 in-Ibs
275 in-Ibs
275 in-Ibs
275 in-Ibs
275 in-Ibs
275 in-Ibs
13
+