UPS Connections
Terminal Block
The following illustration is a detail view of the terminal block and wiring connections used
for 208/240 volt units (see pages 45-46 for terminal block location).
Notes:
1) If ac input power is 240Vac rated, terminals 12 and 13 must be shorted by jumper wire
Do not jumper terminal 11 to 12 or
2) If ac input power is 208Vac rated, terminals 11 and 12 must be shorted by jumper wire
Do not jumper terminal 13 to 12 or
Wire Size and Tightening Torque
Use the following table to select the recommended wire size and terminal lug tightening torque
for I/O wire connections. Note: The bold number in () is the maximum size wire that the
terminal block can accomdate.
Item
Terminal
Number
AC input lines
1 and 2
AC output lines
4, 5, and 7
AC output neutral
Ground
3 and 8
EPO switch
14 and 15
Remote Switch
16 and 17
TOSHIBA
AWG
AWG
3.6kVA
6kVA
(8) 12
(8) 10
(8) 12
(8) 10
6
(8) 12
(8) 10
(8) 12
(8) 10
16
16
16
16
13.
11. Factory Setting is 208Vac.
AWG
AWG
8kVA
10kVA
(1/0) 8
(1/0) 6
(1/0) 8
(1/0) 6
(1/0) 8
(1/0) 6
(1/0) 8
(1/0) 4
16
16
16
16
(1 Newton-meter = 8.8 pound-inches)
13
AWG
Tightening Torque
14-18kVA
(Pounds-Inches)
(1/0) 4
14.2
(1/0) 4
14.2
(1/0) 4
14.2
(1/0) 4
14.2
16
9.0
16
9.0