Ups Connections; Terminal Block - 208/240; Out - Toshiba 1600XP SERIES Installation And Operation Manual

Hide thumbs Also See for 1600XP SERIES:
Table of Contents

Advertisement

8. UPS Connections

8.1 Terminal Block - 208/240 V
The following illustration is a detail view of the terminal block and wiring connections used for 208/240
volt units (see "Appendix C: 1600XP/1600XPi Dimensions and Weights" on page C1).
1
2
3
4
G
X1
L1 (L*)
L2 (N*)
208/240 V
in
INPUT
* – If only one input line is hot, connect hot line to terminal 1 (L), and connect the Neutral line to terminal 2 (N).
NOTE 1 – If AC input power is 208 Vac rated, short terminals 11 and 12 with a jumper wire. DO NOT jumper terminal 13 to 12 or
11. Factory Setting is 208 Vac. Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
NOTE 2 – If AC input power is 240 Vac rated, short terminals 12 and 13 with a jumper wire. DO NOT jumper terminal 11 to 12 or
13. Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
NOTE 3 – EPO and Rmt Contacts function – See Section 8.2
1600XP/XPi Series Installation and Operation Manual – 60616-012
, 120/280/240 V
IN
Factory Installed N - G Jumper
5
6
7
8
X2
X3
G
N (0V)
32 V
88 V
120 V
120 V
208 V
240 V
OUTPUT

OUT

1,2
11
12
13
14
208
COM 240
EPO1
EPO2
208V
240V
NO
Jumper selection
See notes 1&2
EPO
15
16
17
REMOTE1
REMOTE2
NO
3
Rmt Contacts
3
11