1 .3.4 Complete Shutdown - Toshiba G8000U Series Operation Manual

Ups toshiba g8000u series
Table of Contents

Advertisement

TOSHIBA
1 1 .3.4
Complete Shutdown
This section shows the procedure to turn off the control power and shut down the UPS
completely.
Step
1 -3
Same as steps 1 -3 in Section 1 1 . 3 . 3 "Stop."
4
Scroll the LCD screen
to see the DC I N PUT
and make sure DC bus
voltage is OV.
(see 1 0 .2.4 "LCD
Scroll" on page 36)
5
Turn off the control
power supply switch
(8A) *
6
Turn off all breakers at
A C output, Bypass
I nput & AC Output.
*
This operation is different from the displayed instruction on the screen .
B e sure t o perform the procedu re specified here.
Table 1 1 .4 Complete Shutdown
Procedu re
Noth ing is displayed on the LCD and all LEOs are off.
( Sh utdown is completed and U PS is isolated . )
LCD/LE D Status
DC INPUT
DC-V
O[V]
BATT-V
O[V]
BATT- I
O[A]
- 40 -
6F3H1048