UPS Connections

Terminal Block
The following illustration is a detail view of the terminal block and wiring connections used for 208/240 volt
units (see
pages
52-53 for terminal block location).
NOTE
1 If AC input power is 240Vac rated, terminals 12 and 13 must be shorted by jumper wire DO NOT jumper
terminal 11 to 12 or 13.
2 If AC input power is 208Vac rated, terminals 11 and 12 must be shorted by jumper wire DO NOT jumper
terminal 13 to 12 or 11. Factory Setting is 208Vac.
Wire Size and Tightening Torque
Use the following table to select the recommended wire size and terminal lug tightening torque for I/O
wire connections.
Note: The bold number in () is the maximum size wire that the terminal block can accommodate.
Terminal
Item
Number
AC Input Lines
1 and 2
AC Output Lines
4, 5, and 7
AC Output Neutral
Ground
3 and 8
EPO Switch
14 and 15
Remote Switch
16 and 17
(1 pound-inch = 0.11 Newton-meter)
16
AWG
AWG
3.6kVA
6kVA
(8) 12
(8)
10
(8) 12
(8)
10
6
(8) 12
(8)
10
(8) 12
(8)
10
16
16
16
16
AWG
AWG
AWG
8kVA
10kVA
14-18kVA
(1/0)
(1/0)
(1/0)
8
6
(1/0)
(1/0)
(1/0)
8
6
(1/0)
(1/0)
(1/0)
8
6
(1/0)
(1/0)
(1/0)
8
4
16
16
16
16
16
16
AWG
Tightening Torque
22kVA
(Pounds-Inches)
(1/0)
14.2
4
1
(1/0)
14.2
4
1
(1/0)
14.2
4
1
(1/0)
14.2
4
1
16
9.0
16
9.0