3.0 UPS Power Connections

The following illustration shows the wiring connections from the power distribution
panel (not part of the UPS) to the UPS, and from the UPS to the battery cabinet. This
connection diagram is to be used with the UE31-BC-0650 Battery Unit.
3.1

UPS Input Voltage

If the UPS AC input power is 208 V rated connect a jumper wire between terminals 11
and 12 on the UPS terminal block. DO NOT jumper terminal 13 to 11 or 12. The UPS
ships from the factory with the jumper in the 208 V position.
If the UPS AC input power is 240 V rated connect a jumper wire between terminals 12
and 13 on the UPS terminal block. DO NOT jumper terminal 11 to 12 or 13.
3.2

Connecting Multiple Battery Cabinets

Up to two battery cabinets may be connected in parallel to the UPS. To connect two
battery cabinets to the UPS,
1. Connect the first battery cabinet to the UPS as shown in the illustration above.
2. Connect cabinet 2 CN12A to cabinet 1 CN22,
3. Connect cabinet 2 CN13A to cabinet 1 CN23,
4. Connect cabinet 2 CN14A to cabinet 1 CN24.
3.3

Battery Cabinet Cabling

The battery cabinets ship with a set of six-foot long cables. Contact Toshiba Customer
Support at 1-877-867-8773 if longer cables are required for your application, or if
additional cables or connectors are required.