9.2.2

Operating Buttons

Table 9.3 shows the functions of the operating buttons on the graphic panel.
NOTES
No.
Name
(2)
RUN
(3)
STOP
(4)
UPS
(5)
BYPASS
(6)
FLOAT
(7)
SCROLL UP
(8)
SCROLL DOWN
(9)
RESET
Keep an operating button pressed for 0.5 seconds at least, when changing
UPS modes.
Keep the reset button pressed for 5 seconds to reset the UPS.
The U PS may not respond if this d u ration is too short.
Table 9.3 Button fu nction
Function
To start up the UPS.
To stop the UPS.
To transfer to normal operation
from bypass operation
To transfer to bypass operation
from normal operation
/
EQUAL
To flip the recharge mode
between float charge and
equalize charge.
To scroll the LCD screens.
To reset the UPS faults and
warnings shown on the LCD.
Remarks
The UPS starts up when this button is
pressed.
(Key-Switch in OPERATION mode)
The UPS stops when this button is
pressed.
(Key-Switch in OPERATION mode)
The UPS transfers to normal
operation, if this button is pressed while
bypass operation.
(Key-Switch in OPERATION mode)
The UPS transfers to bypass
operation, if this button is pressed while
normal operation.
(Key-Switch in OPERATION mode)
The UPS flips recharge voltage
between float charge
Equalize charge voltage can be
programmed as protection charge, with
battery overheat contact on, if desired.
(Key-Switch in OPERATION mode)
See Section 1 2.2.4 " LCD Scroll with
faults or warnings" and Section 1 0.2.4
" LCD Scroll" for details.
- 26 -
6F3H1048
&
equalize charge.