1 .3.3 Stop - Toshiba G8000U Series Operation Manual

Ups toshiba g8000u series
Table of Contents

Advertisement

TOSHIBA

1 1 .3.3 Stop

Table 11.3 shows the procedure to stop the UPS.
Step
Transfer to Bypass
supply as described i n
Table 1 1 .2 .
2
Turn off the DC i nput
breaker, and,
Press the "STOP"
button [(3) i n Figure
9 .2 . 1 on page 25] for
0.5 sec at least.
3
Please wait.
- Procedu re completed .
Table 1 1 .3 Stop
Procedu re
U PS LED is off & BYPASS LED is o n .
BATTERI ES LED is off & I NVERTER LED flashes then off.
FLOAT CHARG E LED & CONVERTER LED are off.
G
LCD/LE D Status
BYPASS
AC-VO 480[V]
AC- I O
50[%]
PRESS 'UPS' SWITCH
BYPASS
M OVE #728 TO 'O FF' POSITION
BYPASS
PRESS 'RUN' SWITCH
- 39 -
6F3H1048
SWITCH

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents