2.2.3 Fau Lt Messages - Toshiba G8000U Series Operation Manual

Ups toshiba g8000u series
Table of Contents

Advertisement

TOSHIBA
1 2.2.3
Fau lt Messages
Figures 12.6 show the locations for fault detection. Tables 12.4 through 12.8 list the fault
messages described in Section 12.2.1 " Fault Data Screen". The content and display text for the
fault and warning messages are in Tables 12.4 through 12.8. UPS's can be shipped with
different protective configurations from the standard shown in figure 12.6, if specified by the
customer. See the protective configuration indicated on the single line diagram for each UPS.
478
958
#
Item
1
7 1 F
2
30ST
3
80PS
4
80B2
S
48
6
76
7
26
8
SE
59C
47C
27C
Figure
1 2.6
Protective Detector Locations
Table
LCD Message
Ind ication
FUSE BLOW N
(No indication)
CONT. PS. E R R
BATT. UV
START U P ERR
DC OC
OVE R H EAT
E M G . STOP
- 47 -
U PS
1 2.4
Fau lt (Trip)
Description
AC or DC Main circuit fuse blown .
An error occu rred i n the main control
microprocessor (C P U ) .
T h e control power supply voltage fai led.
Battery voltage is below cutoff voltage.
Startup was not completed i n a time frame .
Over-cu rrent i n DC circuit.
Temp High i n the cabinet.
An emergency stop was activated by the external
contact
6F3H1048
T
83MC2
83BF