Vertical Terminations - Regency Horizon HZ30E-NG10 Owners & Installation Manual

Horizon hz30e series gas fireplace
Hide thumbs Also See for Horizon HZ30E-NG10:
Table of Contents

Advertisement

Two 45
elbows equal to one 90
o
Vent must be supported at offsets.
Minimum distance between elbows is 1 ft. (305mm).
Maintain clearances to combustibles as listed in the "Clearances" section.
Horizontal vent must be supported every 3 feet.
Firestops are required at each floor level and whenever passing through a wall.
Must use optional rigid pipe adaptor (Part# 510-994. when using rigid pipe vent systems.
Vertical Venting with Two (2. 90
One 90
elbow = Two 45
o
Option
V
H
A)
1' Min. 4' Max.
B)
2' Min. 5' Max.
C)
3' Min. 6' Max.
D)
4' Min. 7' Max.
E)
5' Min. 8' Max.
Restrictor Position - Set 0 (factory setting)
V1

VERTICAL TERMINATIONS

elbow. Maximum of four 45
o
Elbows
o
elbows.
o
V + V1
With these options,
maximum total pipe
2' Min.
length is 28 feet with
minimum of 6 feet total
3' Min.
vertical and maximum 8
feet total horizontal.
4' Min.
Please note minimum
5' Min.
1 foot between 90
elbows is required.
6' Min.
V
H
"
RIGID PIPE 4" X 6-5/8
elbows allowed, not including the starting 45
o
Vertical Venting with Two (2. 90
Option
A)
B)
C)
D)
o
E)
V
H1
installation
elbow at the flue collar.
o
One 90
elbow = Two 45
o
o
H + H1
V
With these options, maximum
total pipe length is 28 feet
2' Max.
2' Min.
with minimum of 6 feet total
vertical and maximum 6 feet
3' Max.
3' Min.
total horizontal.
4' Max.
4' Min.
Please note minimum 1
foot between 90
5' Max.
5' Min.
required.
6' Max.
6' Min.
Restrictor Position - Set 0 (factory setting)
H
Regency Horizon HZ30E-10 Gas Fireplace
|
31
Elbows
o
elbows.
elbows is
o
|
31