The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fireplace and vent system be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
Clearance:
A: Sidewall (on one side)
B: Ceiling
(room and/or alcove)
C: Mantel Height (min.)
D: Mantel Depth (max.)
E: Alcove Width
F: Alcove Depth
G: From Floor
Note:
D
G
10 |
Regency Horizon HZ30E-10 Gas Fireplace
CLEARANCES
Dimension
Measured From:
8" (203mm)
Side of Fireplace Opening
39" (991mm)
Top of Fireplace Opening
13-1/4" (330mm)
Top of Fireplace Opening
21-1/4" Above Fireplace
12" (305mm)
Opening
60" (1524mm)
Sidewall to Sidewall (Minimum)
36" (914mm)
Front to Back Wall (Maximum)
21" (533mm)
Top of Fireplace Opening
0"
F
A
E
Installed Close
to Floor
F
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fireplace and vent
system be installed only in accordance with these instructions.