Moving to the Advanced Function Setting Level

Moving to the Advanced Function Setting Level for the First Time
(i.e., with the Default Settings)
To enter the Advanced Function Setting Level, you must first enter the Protect Level and change the
setting of the icpt (Initial Setting/Communications Protect) parameter to 0 (enable moving to
Advanced Function Setting Level) to clear the protection.
Clearing Protection
1
Press the O and M Keys simultaneously for at least 3
seconds* in the Operation Level.
The No. 1 display will flash when the key is pressed for 1 s or
longer.
*
The key pressing time can be changed in the Move to Protect Level
Time parameter in the Advanced Function Setting Level.
The display will change to the Protect Level.
2
Press the M Key once at the Operation/Adjustment Protect
parameter.
The display will change to the Initial Setting/Communications
Protect parameter.
3
Press the D or U Key at the Initial Setting/Communications
Protect parameter to change the set value to 0 (enable moving
to Advanced Function Setting Level).
Now the amoV (Move to Advanced Function Setting Level)
parameter can be displayed in the Initial Setting Level.
The default is 1 (disable moving to Advanced Function Setting
Level).
4
Press the O and M Keys simultaneously for at least 1 second
in the Protect Level.
The display will change from the Protect Level to the Operation
Level.
E5@C Digital Temperature Controllers User's Manual (H174)
4 Basic Operation
Operation Level
25
0
Protect Level
oapt
Operation/
Adjustment
0
Protect
Initial Setting/
icpt
Communications
Protect
1
1: Moving to
Advanced
Function Setting
Level is disabled.
Protect Level
icpt
Initial Setting/
Communications
0
Protect
Operation Level
25
PV/SP
0
4 - 5
4