This parameter sets whether the set point that triggers the alarm is the ramp SP or target SP.
Setting
Related Parameters
SP Ramp Set Value and SP Ramp Fall Value (Adjustment Level): Page 6-33
See
See
ST (Self-tuning) (Initial Setting Level): Page 6-45
rs-t
This parameter sets the input type for the remote SP.
Function
4-20: 4 to 20mA
Setting
0-20: 0 to 20mA
1-5v: 1 to 5V
0-5v: 0 to 5V
0-10: 0 to 10V
rspu
This parameter is set to ON to enable setting SP Mode. You can set the SP Mode parameter
to LSP to select a local SP or to RSP to select a remote SP. If this parameter is set to OFF,
only a local SP can be used.
Function
Setting
Related Parameters
See
See
SP Mode (Adjustment Level): Page 6-21
E5@C Digital Temperature Controllers User's Manual (H174)
000
Alarm SP Selection
Setting range
sp-m: Ramp SP, sp: SP
000
Remote SP Input
Setting range
000
Remote SP Enable
Setting range
on: Enabled or off: Disabled
Alarm 1 to alarm 4 must be assigned.
The SP Ramp Set Value parameter must not be set
to OFF and the SP Ramp Fall Value parameter must
not be set to SAME or OFF. The ST parameter must
be set to OFF.
The alarm type must be set to 1, 2, 3, 4, 5, 6, 7, 14,
15, 18, or 19.
Default
sp-m
There must be a remote SP input.
Default
4-20
There must be a remote SP input.
The ST parameter must be set to OFF.
Default
off
6 Parameters
6
6 - 81