6 Parameters
alma
You can use the integrated alarm to output an OR of alarm 1, alarm 2, alarm 3, alarm 4, the
HB alarm, the HS alarm, the input alarm, and the RSP input alarm. Set this parameter to the
sum of the codes of the status for which to output an OR.
Function
The default is 49 (i.e., an OR of alarm 1, the HB alarm, and the HS alarm is output). The
alarm 1 code is 1, the HB alarm code is 16, and the HS alarm code is 32: 1 + 16 + 32 = 49.
Setting
Related Parameters
See
See
Alarm Value 1 to 4 (Operation Level): Page 6-14
MV at Error (Adjustment Level): Page 6-33
HB ON/OFF (Advanced Function Setting Level): Page 6-63
HS Alarm Use (Advanced Function Setting Level): Page 6-74
Remote SP Enable (Advanced Function Setting Level): Page 6-81
t-u
• Set the soak time unit for the simple program function.
Function
Setting
Related Parameters
See
See
Program Start (Operation Level): Page 6-12
Soak Time Remain (Operation Level): Page 6-13
Soak Time (Adjustment Level): Page 6-31
Wait Band (Adjustment Level): Page 6-32
Program Pattern (Initial Setting Level): Page 6-46
6 - 80
Integrated Alarm Assignment
Code
Status
+1
Alarm 1
+2
Alarm 2
+4
Alarm 3
+8
Alarm 4
+16
HB alarm
+32
HS alarm
+64
Input error
+128
RSP input error
Setting range
Default
0 to 255
000
Soak Time Unit
Setting range
Default
m: Minutes, h: Hours
The integrated alarm must be assigned.
49
The Program Pattern parameter must not be set to
OFF.
m