Omron E5C User Manual page 207

Digital temperature controllers
Hide thumbs Also See for E5C:
Table of Contents

Advertisement

ON
OFF
−100%
PV Dead Band
When the PV enters the PV dead band, any unnecessary output is stopped to prevent the valve
from deteriorating.
SP
PV
Manual MV, MV at Stop, and MV at PV Error
Refer to the following sections.
Manual PV: 5-12-1 Manual MV
MV at Stop and MV at PV Error: 5-15 Output Adjustment Functions
Related Displays and Parameters
Parameter name
Close/Floating
Motor Calibration
Travel Time
Valve Opening Monitor
Position Proportional Dead
Band
Open/Close Hysteresis
PV Dead Band
* Motor calibration not performed, potentiometer not connected, or potentiometer input error.
E5@C Digital Temperature Controllers User's Manual (H174)
Open/Close Hysteresis
Position Proportional
Dead Band
0
Unnecessary output is
stopped in this range.
Display
Set (monitor) values
clfl
FLOT: Floating control
CLOS: Close control
calb
OFF
ON
ERR (Error occurred.)
mot
0 to 999 (s)
Normal: −10.0% to 110.0%
V-m
Error: ----*
db
Close control: 0.1% to 10.0%
Floating control: 0.1% to
10.0%
oc-h
0.1 to 20.0
p-db
0 to 9999
5 Advanced Operations
MV − Valve opening
100%
PV Dead Band
Default
Level
FLOT
OFF
Initial Setting
Level
30
---
Operation Level
4.0
2.0
Adjustment Level
0.8
0.0
Advanced
Function Setting
Level
5
5 - 59