E5Dc Terminal Block Wiring Example - Omron E5C User Manual

Digital temperature controllers
Hide thumbs Also See for E5C:
Table of Contents

Advertisement

2-2-4

E5DC Terminal Block Wiring Example

Terminal Arrangement
The terminals block of the E5DC is divided into five types of terminals: control output 1, sensor input, auxiliary
outputs, input power supply, and options.
Input power supply
Options
Precautions for Correct Use
When you purchase the Digital Controller, it will be set for a K thermocouple (input type = 5). If a
different sensor is used, an input error (s.err) will occur. Check the setting of the Input Type
parameter.
Control Output 1
Model Numbers
The specification for control output 1 is given in the following location in the model number.
E5DC-@@ @ @ S M-@@@
Code
RX
1 relay output
QX
1 voltage output (for driving SSR)
CX
1 linear current output
Terminal Details
RX
E
Control Output 1
F
E5@C Digital Temperature Controllers User's Manual (H174)
Control output 1
1
5
9
Auxiliary outputs
2
6
10
11
12
Sensor input
3
7
13
4
8
14
Control output 1
Output type
Relay
Control output 1
output
Specifications
250 VAC, 3 A (resistive load)
12 VDC, 21 mA
4 to 20 mA DC or 0 to 20 mA DC with load of 500 Ω max.
QX
E
+
Voltage output
Control Output 1
F
(for driving SSR)
2 Preparations
CX
E
+
Linear current
F
output
2 - 25
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

H174-e1-05 series

Table of Contents