Advertisement

installation
|
28

alloWaBle Vertical terMinations for HZ54e-lp

The shaded area in the diagram shows all allowable
combinations of straight vertical and offset to vertical
terminations, using two 90
elbows, with rigid pipe Venting
o
Systems for Propane. Two 45
elbow. Maximum of four 45
elbows allowed.
o
Please note min. 1 foot between 90
elbows is required.
Vent must be supported at offsets.
Firestops are required at each floor level and
whenever passing through a wall.
Maintain clearances to combustibles as listed in
the "Clearances" section.
Refer to the "Vent Restrictor Position" section for
details on how to change the vent restrictor from
the factory setting of Set 1 to Set 4 or Set 5
if required.
Note: Must use optional flue adaptor when using
Rigid Pipe (Part # 770-994).
28 |
Regency Horizon HZ54E-10 Gas Fireplace
VentinG arranGeMents
elbows equal to one 90
o
o
o
2
4
0
40
38
36
34
32
30
Vent Restrictor on Set 5
28
26
24
22
Vent Restrictor on Set 4
20
18
16
14
12
10
8
6
4
2
0
Max. 10' (3m)(centerline to centerline)
Minimum length of pipe
between elbows 12" (305mm)
Horizontal (Feet)
8
6
10
12
Vent Restrictor on Set 1
(factory setting)
14
18
16