Page 1
Installation Manual Gas Fireplace MODELS: HZ54E-NG10 Natural Gas HZ54E-LP10 Propane www.regency-fire.com Horizon HZ54E Product Video WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage. - Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Page 2
Warnock Hersey/Intertek for both safety and efficiency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your Regency Fireplace.
MANUFACTURED MOBILE HOME REQUIREMENTS INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE This Regency product has been tested and listed by Warnock Hersey/Intertek as a Direct Vent Wall Furnace to the following ® standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88-2014 / CSA 2.33-2014 and GAS-FIRED APPLIANCES FOR USE AT HIGH ALTITUDES CAN / CGA 2.17-M91.
Allowable Vertical Terminations for HZ54E-ng ..27 Accessories ..............59 Venting Arrangements ..........28 Allowable Vertical Terminations for HZ54E-lp ..28 Warranty Unit Installation with Horizontal Termination ....29 Unit Installation with Vertical Termination ....30 The Warranty: Limited Lifetime ........60 Unit Installation ............31 ® Regency Horizon HZ54E-10 Gas Fireplace...
This is a copy of the label that accompanies each HZ54E-NG10/HZ54E-LP10 Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review. NOTE: Regency units are constantly being ® improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipm ent, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation. ® Regency Horizon HZ54E-10 Gas Fireplace...
UNIT DIMENSIONS FACEPLATE & DOOR FRAME OVERLAY DIMENSIONS The Verona Glass Surround (Not Shown) Dimensions: 58-9/16" W x 27-1/8" H Regency Horizon ® HZ54E-10 Gas Fireplace...
National Electrical Code, ANSI/NFPA 70 or CSA C22.1 Canadian Electrical Code. 3) See general construction and assembly in- structions. The appliance and vent should be enclosed. ® Regency Horizon HZ54E-10 Gas Fireplace...
The Heat Release Kit expels warm air from the fireplace to the outside of the building, allowing the fireplace to be operated with less heat entering the room. The kit may be used on either the left or right side. Regency Horizon ® HZ54E-10 Gas Fireplace...
Installed Close Installed Close to Ceiling to Floor NON-COMBUSTIBLE REQUIREMENTS Metal Stud (header) 60-1/2" (1537mm) Wood Stud Wood Stud Non-combustible Material 52-7/8” Non-combustible Material 3-7/8" 5-1/2” ( 99mm) (140mm) 10 | ® Regency Horizon HZ54E-10 Gas Fireplace...
While every precaution is taken in providing the recommendations on preparation and finish, given the variations in paint quality, with temperature limits and workmanship in application, Regency is unable to guarantee the life of the joint compounds, paint or any other finish materials or workmanship applied to or used in any application surrounding the fireplace.
Opening To Unit Base Legs MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram: 4 (102mm) MANTEL LEG Non-Combustible 1.5" (38mm) 5-1/2 (140mm) Allowable mantel leg projection 8 (203mm) 11 (279mm) 12 | ® Regency Horizon HZ54E-10 Gas Fireplace...
52-7/8 ” Unit shown without faceplate for Illustrative purposes only NOTE: The Verona Glass Surround (not shown) opening needs to be 60-1/16" W x 28 5/8" H Regency Horizon ® HZ54E-10 Gas Fireplace...
Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited. Remove screws to Standoff Diagram 2 release standoffs 14 | ® Regency Horizon HZ54E-10 Gas Fireplace...
& wall finishes. Important: The minimum framing dimensions given for height, width and depth must be maintained even if using non combustible materials. Dangerous operating conditions will occur if minimum framing dimensions are not adhered to. Regency Horizon ® HZ54E-10 Gas Fireplace...
4. Attach both vertical studs (478-015) and secure using 6 screws (2 at bottom, 2 at top and 2 on the sides) as shown NOTE: Ensure the flat side of the steel stud is facing the wood framing. 16 | ® Regency Horizon HZ54E-10 Gas Fireplace 09.15.14 919-441...
11. Using the two (2) screws provided secure the cover plate to the Receiver. Low Voltage Junction Box Profl ame Receiver J-Box Receiver Slider Switch Wall Plate 10 ft. wire harness with 12 pin connector Diagram 1 Regency Horizon ® HZ54E-10 Gas Fireplace...
THIS HOLE SETS THE VENTR ESTRICTOR VENT RESTRICTOR AT 2-1/2 AT 1 Vent Restrictor Set 5 Vent Restrictor Set 3 SET 4 THIS HOLE SETS THE VENTR ESTRICTOR AT 2 Vent Restrictor Set 4 18 | ® Regency Horizon HZ54E-10 Gas Fireplace...
* Clearance in accordance with local installation codes and the requirements of the gas supplier 3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly 3 feet (91cm) above - if within 10 feet (3m) horizontally Regency Horizon ® HZ54E-10 Gas Fireplace...
2) Only Flex pipe purchased from FPI may be used for Flex installations. 3) Horizontal vent must be supported every 3 feet. 4) A wall thimble is mandatory for all horizontal terminations due to high temperatures. 20 | ® Regency Horizon HZ54E-10 Gas Fireplace...
Direct Vent Pro, ICC Excel and Selkirk ® Direct-Temp. AstroCap XL is a proprietary trademark of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc. Regency Horizon ® HZ54E-10 Gas Fireplace...
Set 1 to Set 2 or vent restrictor from the factory setting of Set 1 to Set 4 if required. Set 3 if required. Note: Regency Direct Vent System (Flex) is only approved for ®...
Page 25
5' Min. 4' Max. 10' Min. 7' Max. between 90 elbows is 6' Min. 6' Max. 11' Min. 9' Max. required. VENT RESTRICTOR SETTING: Vent restrictor factory set at Set 1, no adjustment required. Regency Horizon ® HZ54E-10 Gas Fireplace...
Page 26
Please note min. 1 foot 5' Min. 6' Max. 8' Min. between 90 elbows is 6' Min. 8' Max. 9' Min. required. VENT RESTRICTOR SETTING: Vent restrictor factory set at Set 1, no adjustment required. 26 | ® Regency Horizon HZ54E-10 Gas Fireplace...
Set 1 to Set 2 or Set 4 if required. Note: Must use optional flue adaptor when using Rigid Pipe (Part # 770-994). Max. 10 (3m)(centerline to centerline) Minimum length of pipe between elbows 12 (305mm) Regency Horizon ® HZ54E-10 Gas Fireplace...
Set 1 to Set 4 or Set 5 if required. Note: Must use optional flue adaptor when using Rigid Pipe (Part # 770-994). Max. 10 (3m)(centerline to centerline) Minimum length of pipe between elbows 12 (305mm) 28 | ® Regency Horizon HZ54E-10 Gas Fireplace...
“Mill-Pac” sealant (supplied) to every inner pipe connection. Failure to do Diagram 4 so may result in drafting or performance issues not covered under warranty. Regency Horizon ® HZ54E-10 Gas Fireplace...
Diagram 5 or local codes. Note that for steep roof pitches, the vertical height must be increased. Diagram 3 30 | ® Regency Horizon HZ54E-10 Gas Fireplace...
1-3/8"(35mm) and fasten with the 3 screws. NOTE: Horizontal sections must be supported at intervals not exceeding 3 feet (0.9 Fourrures en bois meter). (Flame picture and performance will be affected by sags in the liner). Regency Horizon ® HZ54E-10 Gas Fireplace...
(CAN1 2.17-M91). Ignitor Pilot GAS LINE Note: If you have an incorrect flame pattern, INSTALLATION contact your Regency dealer for further ® instructions. Since some municipalities have additional local codes it is always best to consult with Incorrect flame pattern will have small, probably...
2) The valve cover is located on the right side underneath the glass door - loosen 2 screws securing the valve cover (see Diagram 1 below). Diagram 3 Diagram 1 Valve cover 3) Slide the valve cover upward. Diagram 2 Regency Horizon ® HZ54E-10 Gas Fireplace...
NG with Logs Full open NG with Stones Full open 1/2" LP with Logs Full open LP with Stones Full open CAUTION: Carbon will be produced if air shutter is tightly closed. Venturi Cap 34 | ® Regency Horizon HZ54E-10 Gas Fireplace...
Caution: Ensure that the wires do not touch any hot surfaces and are away from sharp edges. CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Regency Horizon ® HZ54E-10 Gas Fireplace...
NOTE: When the remote receiver is set to ON position, the remote control transmitter and all of its features are now dis- abled. CAUTION Do not wire Thermostat wires to 120V wire. 36 | ® Regency Horizon HZ54E-10 Gas Fireplace...
Bracket Fit side panel tab into slot Right side back panel tab fi tted into slot Left side panel in position Bracket shown in place on right side of the fi rebox Regency Horizon ® HZ54E-10 Gas Fireplace 10/08/09 918-754a...
Secure template in place with magnets (supplied) on each side. These cut lines for HZ40E only HZ54E - existing Pilot HZ54E - new Pilot Hood Top View - showing both HZ54E/HZ40E cut Hood template out along dotted line Regency Horizon ® HZ54E-10 Gas Fireplace 02.10.16 919-258a...
Page 40
HZ54E shown - Completed Install 14. Carefully remove magnets and log placement template, slightly lifting logs as required. Match pin and pin landing Logs 1 and 3. HZ40E shown - Completed Install 40 | ® Regency Horizon HZ54E-10 Gas Fireplace 919-258a 02.10.16...
Mesh screen from inner door frame (1) to be removed and installed into outer door frame (3) as shown. Bend the six tabs down to secure the mesh to the outer door frame. Tabs 12.15.14 919-387 Regency Horizon ® HZ54E-10 Gas Fireplace...
There is a top and bottom, the top of the faceplate has a full 1" return whereas the bottom only has a 1/2" return as shown in the diagram below. 42 | ® Regency Horizon HZ54E-10 Gas Fireplace 919-387 12.15.14...
Page 43
Also if necessary, the faceplate may be adjusted up and down by loosening the top screw as shown in the diagram below and sliding the plate up or down as required. Faceplate Mounting Slots Completed Faceplate Installation Regency Horizon ® HZ54E-10 Gas Fireplace 919-387 12.15.14...
Aerial View of the inside of the unit shown. 7) Remove bottom cover by undoing 3 screws securing it to the firebox base, lift up and out. Aerial View of the inside of the unit shown. 44 | ® Regency Horizon HZ54E-10 Gas Fireplace...
Page 45
12) Remove 8 screws to remove the fan access panel cover - located on Ground Lug the left hand side floor of the firebox. 16) Slide the thermodisc into the bracket on the bottom side of the fan access panel - check fan access panel gasket - replace if necessary. Fan Access Panel Regency Horizon ® HZ54E-10 Gas Fireplace...
Page 46
These fans collect a lot of dust from within your home. Ensure you maintain these fan motors on a regular basis by vacuuming the fan blades and housing using a soft brush nozzle. 46 | ® Regency Horizon HZ54E-10 Gas Fireplace...
Caution: Ensure that the wires do not touch any hot surfaces and are away from sharp edges. CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Regency Horizon ® HZ54E-10 Gas Fireplace...
1. Turn the wall mounted switch or remote to the "OFF" position. 2. Press "OFF" on the remote control. ON/OFF Button 3. Turn the gas control knob to the "OFF" position to turn off the pilot. Diagram 2 Remote shown in Manual Mode on Hi Regency Horizon ® HZ54E-10 Gas Fireplace...
Utiliser l'interrupteur mural ou la télécommande pour mettre le système sur ''OFF''. Lors de l'entretien de l'appareil –débrancher l'alimentation électrique et couper le gaz de l'appareil. DO NOT REMOVE THIS INSTRUCTION PLATE 919-401a 50 | ® Regency Horizon HZ54E-10 Gas Fireplace...
* Do not strike or abuse the glass. paint and should only be refinished with heat 3) Check for evidences of excessive condensation, * Do not operate this fireplace without the glass resistant paint. Regency uses StoveBright ® such as water droplets forming in the inner front or with a cracked or broken glass front.
4) Remove the door frame overlay by swinging out 45 from the bottom and lift up and out. 6) Remove valve cover - (see valve cover removal section in this manual). 52 | ® Regency Horizon HZ54E-10 Gas Fireplace...
7. Secure the assembly with screws on each side as shown below. 3. Install screen into inner door trim (3). Secure screen by bending down the 6 tabs as shown Tabs Regency Horizon™ HZ40E-10 Gas Fireplace Regency Horizon ® HZ54E-10 Gas Fireplace...
Prior to removing burner - remove the following (if installed): 4) Remove the door frame overlay by swinging out 45 from the bottom -crystals and lift up and out. -pebbles -spa stones -logs -Inner panels 54 | ® Regency Horizon HZ54E-10 Gas Fireplace...
8) Partially lift out valve tray. 9) Disconnect the inlet gas line. Green Wire Orange Wire 4) Disconnect the green ground wire from the valve bracket. 10) Replace valve and reverse steps. Green ground wire Regency Horizon ® HZ54E-10 Gas Fireplace...
9) Partially lift out valve tray. 10) Disconnect the inlet gas line. Burner Bracket 5) With burner removed - lift out burner tray. Gas Inlet Line 11) Replace valve and reverse steps. 56 | ® Regency Horizon HZ54E-10 Gas Fireplace...
FPI is not responsible for results or costs of workmanship of unauthorized FPI dealers or agents in the negligence of their service work. Revision Date: September 2016 Regency Gas Products Warranty 60 | ®...
Page 61
Freight damages for products or parts are not covered under the terms of the warranty. Products made or provided by other manufacturers and used in conjunction with the FPI appliance without prior authorization from FPI may void this warranty. Revision Date: September 2016 Regency Gas Products Warranty Regency Horizon ® HZ54E-10 Gas Fireplace...
Page 62
Product Registration and Customer Support: Thank you for choosing a Regency Fireplace. Regency strives to be a world leader in the design, manufacture, and marketing of hearth products. To provide the best support for your product, we request that you complete a product registration form at http://www.regency-fire.com/Customer-Care/Warranty-Registration.aspx...
Page 63
Product Registration and Customer Support: Thank you for choosing a Regency Fireplace. Regency strives to be a world leader in the design, manufacture, and marketing of hearth products. To provide the best support for your product, we request that you complete a product registration form found on our Web Site under Customer Care within ninety (90) days of purchase.
Page 65
Regency Horizon ® HZ54E-10 Gas Fireplace...
Page 66
66 | ® Regency Horizon HZ54E-10 Gas Fireplace...