Venting Arrangements; Horizontal Termination (Flex) - Regency HZ54E-NG10 Owners & Installation Manual

Regency horizon hz54e gas fireplace
Hide thumbs Also See for HZ54E-NG10:
Table of Contents

Advertisement

installation
|
20
These venting systems, in combination with the HZ54E, have been tested and listed as a direct vent system by Warnock Hersey/Intertek. The location of the
termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section.
FPI Direct Vent (Flex) System Termination Kits include all the parts needed to install the Hz54E using a flexible vent.
notes:
1) Liner sections should be continuous without any joints or
seams.
fpi kit #
Length contains:
#946-615
4 Feet
1)
2)
3)
4)
#946-618
6 Feet
5)
6)
7)
#946-616
10 Feet
8)
9)
10) vinyl siding standoff
20 |
Regency Horizon HZ54E-10 Gas Fireplace

VentinG arranGeMents

HORIzONTAL TERMINATION (FLEx)

regency
8" flexible liner (Kit length)
5" flexible liner (Kit length)
spring spacers
thimble
AstroCap termination cap
screws
tube of Mill Pac
plated screws
S.S. screws #8 x 1-1/2" drill point
Wall Thimble
(Mandatory in all
Horizontal Terminations)
5" dia. flue pipe
8" dia.
Flue pipe
Direct Vent System
®
Vinyl Siding
Standoff
AstroCap XL
Termination Cap
(Part #946-623/P)
spring spacer
2) Only Flex pipe purchased from FPI may be used for Flex
installations.
3) Horizontal vent must be supported every 3 feet.
4) A wall thimble is mandatory for all horizontal terminations
due to high temperatures.
Vent Guard - if required*
(Part #946-506/P)
TM