For any area, the logic numbers of the zones are displayed on the LED / Icon LCD keypad and
logic numbers or zone names of the zones are displayed on the keypad instead of actual
physical numbers. For example: The zones 1, 2, and 3 of 1 area or area 1 displayed on the
keypad are actually zones 20, 31, and 37.
7.4.2

Area Timing

The AMAX panel supports separate entry and exit delay times for each area.
Exit Delay
The programming range is 0 - 255 seconds. In the mode of system arming, the keypad will
beep during exit and will make continuous long beep sound in the last 10 seconds to notify
the exit time is coming to an end.
Entry Delay
The programming range is 0 - 255 seconds. Entry delay time starts when a delay zone is
triggered in armed state.
7.4.3

Common Area

Area 1 can be used as a common area or an independent area. Common area ancillary acts are
as follows:
7.4.4

Keypad Tone / Lockout

Keypad Alarm Tone
The AMAX panel supports to enable or disable keypad alarm tone.
Keypad Lock Count
The number of attempts to enter a wrong user code can be set from 1 to 15 in order to
supervise valid user access. The keypad will be locked for 3 minutes, when the number of
attempts reaches the declared value.
7.5

System

This chapter describes eight categories of system settings including the system date and time,
telephone settings, etc.
7.5.1

System Setting

Date and Time
The AMAX panel has a 24-hour clock and a 12-month calendar that need to be set during
installation. The order is year, month, day, hour, and minute, with each item occupying two
digits [YY] [MM] [DD] [HH] [MM].
Fault Sound Reminder
When the command [2] [1] is used for fault inquiry, the keypad can be programmed to sound
prompt tone to indicate new system fault. The system is defaulted to enable. In case of a new
fault, all keypads will sound a short beep once a minute.
Bosch Sicherheitssysteme GmbH
Only all belonged independent areas are armed, the common area can be armed
When a relevant ancillary area is perimeter arming, the common area will be perimeter
arming too
When a relevant ancillary area is disarmed, the common area will be armed
If any zones under common zones are in triggered or tamper status and the forced arming
is disabled, the common area cannot be armed