Frequency Reference by Pulse Train Input

Frequency reference can be set by pulse train input from the multi-function input
terminal.
• Input pulse specifications
• Low-level voltage: 0.8V or less
• High-level voltage: 3.5 to 32V
• H duty: 30 to 70%
• Pulse frequency: 0 to 33 kHz
• Frequency reference method
Frequency reference is a value obtained by multiplying the ratio of the
maximum input pulse frequency and actual input pulse frequency by the
maximum output frequency.
Reference frequency =
FORWARD RUN/STOP
REVERSE RUN/STOP
PULSE
REFERENCE
DEVICE
Constant
No.
n003
n004
n149
82
Input pulse frequency
Maximum pulse train frequency (n149) × 10
S1
S2
SC
RP
FC
Name
Run command selection
Frequency reference selection
Pulse train input scaling
1=10Hz
× Maximum output frequency (n011)
IM
Run/stop and FWD/REV can
be selected by a switch
connected to the control circuit
terminal.
Frequency setting can be set
by pulse train input signal [0 to
100% (maximum frequency)/
0 to 33kHz] connected to the
multi-function input terminal.
Setting range Initial setting
Unit
1
0 to 3
0 to 9
1
100 to 3300
1
( 33kHz )
( 25kHz )
0
1
2500