Frequency Reference by Pulse Train Input

Frequency reference can be set by pulse train input from the control cir-
cuit terminals.
• Input pulse specifications
• Low-level voltage: 0.8 V or less
• High-level voltage: 3.5 to 13.2 V
• H duty: 30 to 70 %
• Pulse frequency: 0 to 33 kHz
• Frequency reference method
Frequency reference is a value obtained by multiplying the ratio of
the maximum input pulse frequency and actual input pulse fre-
quency by the maximum output frequency.
Reference
frequency
FWD RUN/STOP
REV RUN/STOP
Pulse
Reference
Device
Constant
No.
n003
RUN Command Selection
n004
Frequency Reference
Selection
n149
Pulse Train Input Scaling
Input pulse frequency
=
Maximum pulse train frequency (n149) × 10
S1
SC
RP
Name
6. Programming Features
IM
Run/stop and FWD/REV can be
selected by a switch connected
to the multi-function input.
[Set S1 and S2 to FWD run/stop
(n050 = 1) or REV run/stop (n051 = 2).]
Set the frequency by a pulse-train
input signal [0% to 100%
(maximum frequency)/0 kHz to 33 kHz]
from the control circuit terminal.
Unit
Setting
Range
-
0 to 3
-
0 to 9
1 = 10
100 to 3300
Hz
(33 kHz)
Maximum output
×
frequency (n011)
Factory
Setting
0
0
2500
(25 kHz)