Adjusting speed setting signal

To provide frequency reference by analog input of control circuit terminal FR
or FC, the relationship between analog input and frequency reference can be
set.
MAX. OUTPUT FREQUENCY
GAIN
100
MAX. OUTPUT FREQUENCY
BIAS
100
(a) Analog frequency reference gain (n060)
The frequency reference provided when analog input is 10V (20mA) can
be set in units of 1%. (Max. output frequency n011=100%)
Factory setting : 100%
*
(b) Analog frequency reference bias (n061)
The frequency reference provided when analog input is 0V (4mA or
0mA) can be set in units of 1%. (Max. output frequency n011=100%)
Factory setting : 0%
*
Typical Setting
• To operate the inverter with frequency reference of
0% to 100% at 0 to 5V input
MAX. FREQUENCY (100%)
Gain n060 = 200
Bias n061 = 0
FREQURNCY REFERENCE
0V
10V
(4mA)
(20mA)
(0mA)
(20mA)
0%
0V
( ) indicates the value when current
reference input is selected.
5V
10V
53