Fault Display
Digital
RUN (Green)
Operator
ALARM (Red)
OC
OV
UV1
138
Fault Display and Contents
Inverter
Explanation
Status
OC (Overcurrent)
Inverter output current
momentarily exceeds
approx. 250% of rated
current.
OV (Main circuit over-
voltage)
Protective
Main circuit DC voltage
Operation
exceeds the overvoltage
Output is
detection level because
shut OFF
of excessive regenerative
and motor
energy from the motor.
coasts to
Detection level:
a stop.
200V:Stops at main circuit
DC voltage below
approx. 410V
400V:Stops at main circuit
DC voltage
approx. 820V or more
UV1 (Main circuit low
voltage)
Main circuit DC voltage
drops below the low-
voltage detection level
while the inverter output
is ON.
200V:Stops at main circuit
DC voltage below
approx. 200V(160V
for single-phase)
400V:Stops at main circuit
DC voltage
approx. 400V or more
Causes and
Corrective Actions
• Short circuit or
grounding at inverter
output side
2
• Excessive load GD
• Extremely rapid accel/
decel time
(constants n019 to n022)
• Special motor used
• Starting motor during
coasting
• Motor of a capacity
greater than the inverter
rating has been started.
• Magnetic contactor
open/closed at the
inverter output side
• Insufficient decel time
(constants n020 and n022)
• Lowering of minus load
(elevator, etc.)
• Increase decel time.
• Connect optional
braking resistor.
• Reduction of input
power supply voltage
• Open phase of input supply
• Occurrence of momen-
tary power loss
Check the following :
• Power supply voltage
• Main circuit power
supply wiring is
connected.
• Terminal screws are
securely tightened.