Operator Stop Key Selection - YASKAWA VS-606V7 Series Instruction Manual

Compact general-purpose inverter (voltage vector control)
Hide thumbs Also See for VS-606V7 Series:
Table of Contents

Advertisement

(3) Set carrier frequency selection (n080) to either 1, 2, 3, 4
when using vector control mode. Do not set to 7, 8, or 9.
(4) Carrier frequency is automatically reduced to 2.5kHz when
Reducing carrier frequency selection at low speed ( n175 ) is
set to 1 and the following conditions are satisfied:
Factory setting : 0 ( Disabled )
Operator stop key selection (n007)
Selects processing when STOP key is pressed during operation either from
multi-function input terminal or communications.
Setting
Setting
0
STOP key effective when running either from multi-function input terminals
or communications. When STOP key is pressed, the inverter stops
according to the setting of constant n005. At this time, the digital operator
displays "S P" alarm (blinking). This stop command is held in the
inverter until both forward and reverse run commands are open, or
unitl run command from communications becomes zero.
STOP key ineffective when running either from multi-function input
1
terminals or communications.
Output frequency ≤ – 5Hz
Output current ≥ – 110%
Description
Description
69