YASKAWA VS-606V7 Series Instruction Manual page 95

Compact general-purpose inverter (voltage vector control)
Hide thumbs Also See for VS-606V7 Series:
Table of Contents

Advertisement

Data
• Reference Data (available to read out / write in)
Register No.
0000H
Reserved
0001H
0002H
0003H
0004H-
Reserved
0008H
0009H
000AH-
Reserved
001FH
Note : Write in "0" for unused bit. Never write in data for the reserved register.
• Simultaneous Broadcasting Data (available only for write in)
Register No.
0001H
0002H
Bit signals not defined as the broadcast operation signals are used as the local
station data signals.
bit
0
Run command
1
Reverse run
2
External fault
3
Fault reset
4
Multi-function input reference 1
5
Multi-function input reference 2
6
Multi-function input reference 3
7
Multi-function input reference 4
8
Multi-function input reference 5
9
Multi-function input reference 6
A
Multi-function input reference 7
B - F
(Not used)
Frequency reference (unit : n152)
V / f gain (1000 / 100%)
Multi-function output reference 1
0
(Effective when n057=18)
Multi-function output reference 2
1
(Effective when n058=18)
Multi-function output reference 3
2
(Effective when n059=18)
(Not used)
3 - F
bit
0
Run command
1
Reverse run
2
(Not used)
3
(Not used)
4
External fault
5
Fault reset
6 - F
(Not used)
30000 / 100% fixed unit
(Data is converted into 0.01 Hz inside the inverter, and fractions are
rounded off.)
Description
1 : Run
0 : Stop
1 : Reverse run 0 : Forward run
1 : Fault (EFO)
1 : Reset command
(Function selected by n050)
(Function selected by n051)
(Function selected by n052)
(Function selected by n053)
(Function selected by n054)
(Function selected by n055)
(Function selected by n056)
Setting range : 2.0 to 200.0%
( 1 : MA ON 0 : MA OFF )
( 1 : P1 ON 0 : P1 OFF )
( 1 : P2 ON 0 : P2 OFF )
Description
1 : Run
0 : Stop
1 : Reverse run 0 : Forward run
1 : Fault (EFO)
1 : Fault reset command
95