AT calculated gain
· Usually use the default value.
· Sets the gain when adjusting the PID parameters by auto-tuning.
· To give priority to response, decrease the set value of this parameter. To give priority
Function
to stability, increase the set value of this parameter.
Setting Range
0.1 to 10.0
Comment
F Related parameters
"AT Execute/Cancel" (level 1 mode)
"PID / ON/OFF" (expansion mode)
See
Standby sequence reset method
· Selects the conditions for enabling reset after the standby sequence of the alarm has
been canceled.
· Condition A:
Function
Control started (including power ON), and alarm value, input shift value or set point
(except for changing SP mode or during Remote SP) changed.
· Condition B:
Power ON
0: Condition A / 1: Condition B
Comment
F Related parameters
"Alarm 1 type" "Alarm 2 type" "Alarm 3 type" (setup mode)
See
Unit
None
Setting Range
Expansion Mode
Conditions of Use
The control must be advanced PID con-
trol, and ST must be set to OFF.
Default
1.0
Default
0
5--35