Omron E5AK User Manual page 15

E5ak series digital controller
Hide thumbs Also See for E5AK:
Table of Contents

Advertisement

CHAPTER 1 INTRODUCTION
F Transfer output
1--6
Control outputs 1 and 2 are used depending on the differences in control
method as follows.
Control Method
Standard control
Heating and cooling
control
Position-proportional
control
The E5AK supports the following six transfer outputs.
Set point
Set point during SP ramp
Process value
Heating side manipulated variable
Cooling side manipulated variable
Valve opening
However, note that heating/cooling side manipulated variables can be out-
put only standard type controllers, and valve opening can be output on
position-proportional type controllers
These transfer outputs can be output after being scaled. Setting of an
upper limit value smaller than the lower limit value is allowed, so reverse
scaling can also be carried out.
Model
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
E5AK-PRR2 AC100-240
E5AK-PRR2 AC/DC24
Control Output 1/
Control Output 2
Control output (heat) /
Alarm, etc.,
Control output (heat) /
Control output (cool)
Open/Close

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents