CHAPTER 5 PARAMETERS
Expansion Mode

Automatic return of display mode

· If you do not operate any of the controller keys for the time set in this parameter when
in levels 0 to 2 modes, the display automatically returns to the PV/SP display.
· When this parameter is set to "0", this function is disabled.
Function
· This parameter is invalid while the menu is displayed.
Comment
AT hysteresis
· Usually use the default value.
· The levels of limit cycle operations during AT execution are given hysteresis at event
ON/OFF switching. This parameter sets this hysteresis width.
Function
Comment
LBA detection width
· This parameter can be used when LBA is assigned as an output.
· When the change width of the manipulated variable is below the width set in this
parameter, the controller regards this as detection of an LBA.
Function
Comment
5--36
Setting Range
Unit
0 to 99
Second
Unit
Setting Range
0.1 to 9.9
%FS
Unit
Setting Range
0.0 to 999.9
%FS
Default
0
Conditions of Use
The control must be advanced PID con-
trol, and ST must be set to OFF.
Default
0.2
Conditions of Use
The LBA (Loop Break Alarm) function
must be assigned as an output.
Default
0.2