USS Execution Error Codes

Table 11-6
Execution Error Codes for the USS Instructions
Error Codes
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22

Connecting and Setting Up the MicroMaster Series 3 Drive

Connecting the MicroMaster 3 Drive
You can use the standard PROFIBUS cable and connectors to connect the S7-200 to the
MicroMaster Series 3 (MM3) drive. See Figure 11-5 for the proper cable bias and termination of
the interconnecting cable.
Caution
Interconnecting equipment with different reference potentials can cause unwanted currents to
flow through the interconnecting cable.
These unwanted currents can cause communications errors or damage equipment.
Be sure all equipment that you are about to connect with a communications cable either shares
a common circuit reference or is isolated to prevent unwanted current flows.
The shield must be tied to chassis ground or pin 1 on the 9-pin connector. It is recommended
that you tie wiring terminal 2--0V on the MicroMaster drive to chassis ground.
342
Description
No error
Drive did not respond
A checksum error in the response from the drive was detected
A parity error in the response from the drive was detected
An error was caused by interference from the user program
An illegal command was attempted
An illegal drive address was supplied
The communications port was not set up for USS protocol
The communications port is busy processing an instruction
The drive speed input is out of range
The length of the drive response is incorrect
The first character of the drive response is incorrect
The length character in the drive response is not supported by USS instructions
The wrong drive responded
The DB_Ptr address supplied is incorrect
The parameter number supplied is incorrect
An invalid protocol was selected
USS is active; change is not allowed
An illegal baud rate was specified
No communications: the drive is not ACTIVE
The parameter or value in the drive response is incorrect or contains an error code
A double word value was returned instead of the word value requested
A word value was returned instead of the double word value requested